    The test results for Gradus inserts for stair nosing are shown in Figure 1.

  • All inserts are tested for: slip-resistance, surface roughness, chemical and bacterial/fungal resistance
  • Wear test independently carried out by SATRA using the Taber Abrader Method and classified in accordance with the results shown in Figure 1
  • Slip-resistance tests have been independently undertaken by the Health & Safety Laboratory using the pendulum test (see Figure 2)

Figure 1

Insert Type Composition Environment Slip Potential Stair Nosing Compatibility
Xtra-grip &
Xtra-grip Plus
Pvc with Mineral Aggregate Interior Dry / Wet Conditions Dry Conditions Low
Wet Conditions Low
Aluminium, Bronze, PVC-u
XT & Traditional
Interior Pvc with Natural
Mineral Fillers
Interior Dry Conditions Dry Conditions Low Aluminium, Bronze, PVC-u XT,
Traditional & Elite
Standard Exterior Glass Reinforced Polyester
with Fused Alumina
External Conditions Dry Conditions Low
Wet Conditions Low
Aluminium, Bronze
Traditional
Heavy Duty Exterior Glass Reinforced Polyester
with Fused Alumina
Internal / External Conditions Dry Conditions Low
Wet Conditions Low
Aluminium
Trans-Edge TEX
Stairtile Rubber Composite with
Aggregate Fillers
Internal / External Conditions Dry Conditions Low
Wet Conditions Low
N/A
Wear Classification*
Xtra-grip, Xtra-grip Plus, Interior and Stairtile inserts achieve wear classifications of:
Group T – Class 34 – Commercial Very Heavy
Group T – Class 43 – Light Industrial Heavy

* Stairtile and Interior (standard, grained, Elite) tested to BS EN 660-2:1999 and assessed against the requirements of BS EN 649:1997. Xtra-grip and Xtra-grip Plus tested to BS EN 13845:2005 – 50,000 cycles.

Heavy Duty Exterior and Standard Exterior – Accelerated wear test using a SATRA Pedatron

Figure 2

Pendulum Test Value (PTV) Slip Potential
0 – 24 High Slip Potential
25 – 35 Moderate Slip Potential
36+ Low Slip Potential

 

BS 8300-2:2018 - a PTV of at least 36 is required irrespective of wet or dry conditions